Solutions
Resellers





Contact us!

| |
|
Specifications
A/D CONVERTERS
- Opto 22 SNAP I/O
controllers:
- 16 bits per sample
- 20,000 levels of resolution, 0.005% maximum quantization
error
(when used with 4-20 mA field inputs)
- Pluggable modules available which support a variety of
analog signal standards, with and without optical isolation
between inputs
- Ethernet
- 300-foot maximum distance between PC and controller (can be
extended using Ethernet switches)
- Serial
- Interfaces to PC serial port with RS-485 to RS-232 converter
at
38,400 bits/second (Optomux) or 115,200 bits/second (mistic)
- 4000-foot maximum distance between PC and ADC
- B&B
Electronics 232SDA12
- 12 bits per sample
- 3276 levels of resolution, 0.031% maximum
quantization error (when used with 4-20 mA or 1-5 V field inputs)
- Interfaces
to PC serial port via. RS-232C cable at 9600 bits/second
- Eleven non-isolated 0-5 V field inputs
(convertible from 4-20 mA - see
AquaServ Administrator's Guide)
- 50-foot
maximum distance between PC and ADC (using shielded cable)
- Ideal for temporary or portable AquaServ deployments
TEMPORAL ACCURACY
- Effective A/D converter polling interval:
0.1 seconds (0.5 seconds if using the B&B 232SDA12)
- Real-time totalizers updated every 100 ms
- On-screen chart updated every 5 seconds
- Data stored to disk every 5-1800 seconds
(configurable)
- Temporal resolution depends on horizontal
resolution of screen and printer:
- 113 seconds on a 1024-pixel-wide
display
- 90 seconds on a 1280-pixel-wide
display
- 35 seconds on a 300 DPI printer
- 17 seconds on a 600 DPI printer
MEASUREMENT UNITS SUPPORTED
- Millions of Gallons per Day (MGD) *
- Gallons Per Day (GPD) *
- Gallons Per Minute (GPM) *
- Cubic Feet per Second (CFS) *
- Gallons
- Feet
- Degrees Fahrenheit
- Millions of Liters per Day (MLD) *
- Liters Per Day (LPD) *
- Liters Per Minute (LPM) *
- Cubic Meters per Second (CMS) *
- Liters
- Meters
- Degrees Celcius
- Pulses per Second (PPS) *
- Pulses per Minute (PPM) *
- Milligrams per Liter (mg/L)
- NTU
- Pounds per Square Inch (PSI)
- pH
- Other *
(* = totalizer active. For "Other", the totalizer counts in items per second.)
|
|
|
|